Lodestar CL HV
 +971 555-998-004

Lodestar CL HV

Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Description

Fault indicators for high-voltage lines

Special models of fault indicators Lodestar CL HV for High voltage lines has high designed high noise immunity. Lodestar CL HV has only with visual indication. It is convenient to locate it in a well-viewed area, for example, at the entrance of overhead lines in a substation.

Lodestar CL HV benefits:

• All Lodestar HV indicators are equipped with a short-range radio channel of the Bluetooth Low Energy standard, which allows you to easily configure and adjust the settings from any smartphone with the PPI-3 software installed;
• It is possible to determine the status of the high-voltage line both visually, thanks to the LED indication, and using a portable remote control. (Smartphone with Lodestar App).

Technical specifications

Specifications Lodestar HV Lodestar HV DD
Overhead line voltage class 110 kV
Grid's frequency 50 Hz
Visual indication Ultra-bright LEDs
Detection range up to 100 m (during the day), up to 500 m (at night)
Absolute current response threshold 25 A 20 A
PtG selectivity - Determining the direction
Voltage monitoring +
Remote control (for field config) - Bluetooth BLE (2,4 GHz)
Types of operation control 100 ms, off 0-200 ms
Setting the Reset Timer 6, 12, 24, 48 hours Configurable from 1 h to 8 days
Minimum duration of the emergency process 0,02 s
Resetting the indication • On restoring
• power
• By timer
• By a magnet
• On restoring power
• By timer
• By a magnet
• From a portable remote control
Changing Settings 10 DIP switches • On the short-range radio channel using a portable remote control
• Using KOMORSAN software or SCADA (while indicators connected to Lightbox)
Integration with SCADA systems - While connecting the indicators to the Lightbox, information is exchanged between the KOMORSAN server and the SCADA system via the IEC-104 protocol
Power supply Lithium battery (19 Ah)
Battery life(in standby mode) 8-10 years
Total indication time > 2000 h
Time to failure of the indicator Not less than 60 000 h

 

 

Documentation is provided upon request to the company's clients. Please fill in the form to send a request:

+

By sending this form, I consent to the processing of my personal data.



Our customers

Contact Us

  Office 2107, Iris Bay Tower - Al Mustaqbal St - Business Bay - Dubai - UAE

 

  +971 555-998-004